EVC8-7.2/12-160/250/400/630 Vacuum Contactor High Voltage VCB Contactor for Switchgear
The EVC8-7.2/12-160/250/400/630 vacuum contactor is a high-voltage switching device designed for reliable control and protection of electrical equipment in medium-voltage power systems. It is widely used in switchgear panels, motor starting, transformers, capacitors, and other reactive power compensation devices.
With rated voltage of 7.2kV / 12kV and current options from 160A to 630A, this vacuum contactor ensures excellent electrical performance, compact design, long service life, and safety in operation.
| Name | Unit | Value | |||||||
| Main circuit | Rated working voltage (Ue) | kV | 7.2 | 12 | |||||
| 
 | Rated working current (Ie) | A | 160,250,400,630 | ||||||
| 
 | Rated frequency (fr) | Hz | 50~60 | ||||||
| 
 | Rated making capacity | A | 10Ie (AC-4) | ||||||
| 
 | Rated breaking capacity | A | 8Ie (AC-4) | ||||||
| 
 | Rated short time withstand current | A | 10Ie | ||||||
| 
 | Rated peak withstand current | A | 25Ie | ||||||
| 
 | Rated short circuit duration | s | 4 | ||||||
| 
 | Power frequency withstand voltage | Between phases, phase to earth | kV | 32 | 42 | ||||
| 
 | 
 | Vacuum breaks | kV | 32 | 42 | ||||
| 
 | Lightening impulse withstand voltage | kV | 60 | 75 | |||||
| Control circuit | Rated voltage1 (Us) | V | AC or DC. 110/220 | ||||||
| 
 | Rated power (Ps) | Electric holding | VA | ≤1000/100 (absorbing/holding) | |||||
| 
 | 
 | Mechanical holding | VA | ≤900/600 (closing/opening) | |||||
| Auxiliary circuit | Form | 
 | 3a+3b | ||||||
| 
 | Rated value | 
 | AC380V/5A, DC380V/1A | ||||||
| Control circuit, auxiliary circuit to earth power frequency withstand voltage | kV | 2 | |||||||
| Rated operating frequency | Long-term or mechanical holding type | time/h | 300 | ||||||
| 
 | Short-term | time/h | 600 | ||||||
| Mechanical endurance2 | 10000 times | 30 | |||||||
| Electrical endurance | 10000 times | 10 | |||||||
| Mechanical characteristics | Closing time | ms | ≤200 | ||||||
| 
 | Original opening time | ms | ≤160(electric holding) | ||||||
| 
 | 
 | 
 | ≤60(mechanical holding) | ||||||
| 
 | 3-phase synchronism | ms | ≤3 | ||||||
| 
 | Closing tripping | ms | ≤10 | ||||||
| Remark: 1.rated control voltage can be made according to customer’s requirements. | |||||||||
| 2.for mechanical holding type, the interlock mechanism should be changed every 300,000 times. | |||||||||